Reviewer: 1

Comments to the Author
The paper deals with a complex problem in relation to the erosion of circuit breaker contacts after repeated short circuits.
The work is interesting, but uses approximations and laws that remain valid in well defined experimental conditions. In order to be published, the authors are asked to respond to the following suggestions and remarks.
1. The authors are asked to give in the introduction how they distinguish between the arc resistance and the resistance of circuit breaker poles contacts.
2. Please verify if the pressure of SF6 varies in the same direction than the DRM (dynamic resistance of contact).
3. In figure 1, the authors are asked to give further explanation about the considered values of the capacity C=16.8 mF and L = 0.6 mH.  
4. Figure 5 wants for references and extensive explanations.  
5. Concerning figure 6: The authors are asked to make in which type of breaker this type of arc cutting is operated?  
6. One of the used approximations by authors concerns the mass loss of arcing contact and the cylindrical shape.  The authors are asked to justify this hypothesis.
7. Please give more information concerning the used alloy (CuW80), especially some references where this alloy is currently used.
8. Equation 7 considers the enthalpy of the contacts from 20 °C to the evaporation of the contacts material. This needs further explanation and discussion with regard to the real temperatures at which the contacts are submitted during arcing occurrence.
9. It will be more relevant and necessary to give more justification and explanation concerning equation 10.
10. The value of the determined length decrement of arcing contact (L = 0.268 mm) needs for references and more explanation. What are the works that already determined this length?
11. A comparison between the number of experimental erosion tests and normal life CBs operations is needed.


Reviewer: 2

Comments to the Author
In this manuscript, the authors tried to assess the condition of contact sets in SF6 CBs without dismantling. They used five parameters (Rm average main contact resistance, Ra average arcing contact resistance, Lm length of main contact part, La length of arcing contact part, Lc overtravel) which were extracted from R-L curve, to evaluate the conditions of SF6 contact sets. However, the R-L curve was obtained based on their experimental equipment and the errors of the results were not provided in this paper. So the five parameters extracted from R-L curves were not reliable.
On the other hand, the principle used to define the critical value of the five parameters (Rm, Ra, Lm, La and Lc) was not reliable too. For example, they proposed that the critical values of Rm and Ra, were the highest ones from R-L curve Fig.8. But the reason was not given. So the discussion and conclusion should be invalid.
The current and voltage during the operations were not shown in this manuscript. To assess the contact sets, the authors should compare the R-L curve and the characteristics of current and voltage. Finally, they would give some useful and reliable information. 返回小木虫查看更多

今日热帖
  • 精华评论
  • 国际科学编辑

    reviewer2的意见很negative,估计很玄。建议修改后改投。

  • hequnqun

    楼主你好!请问你在做实验时用到了SF6吧,我想请问你一下,你们是用什么仪器来检测SF6气体的呢?我们实验室现在需要用SF6来作为示踪剂来测量室内外的空气对流速率,所以需要购置一台SF6的定量检测仪器,不需要功能太强大,只是检测线能低一些,最好是能达到0.1ppm,另外,最好不要是手持的那种,希望楼主能给点建议,谢谢!

  • y0920142

    祝福

  • pydc1991

    我也是,一个星期之前收到的消息,被拒然后重投,现在在犹豫是否要重新投,还是换一个EI。

  • hequnqun

    引用回帖:
    6楼: Originally posted by chen89714 at 2016-04-07 12:19:25
    我们做实验时没有用到六氟化硫监测相关的仪器,只是简单通过断路器本身的压力表读取压力数据,具体的你可以咨询下gis方向的,他们应该更清楚。
    ...

    好的,谢谢啦